ID : 5835
Field Bus Parameter Setting
Set the robot controller with teach pendant.
From the top screen—[F4 I/O]—[F6 Aux.]-[F4 Field Bus parameter]
EtherNet/IP IP Address [IP Address]
Set an IP address. If it has already been set, currently set IP address is displayed.
EtherNet/IP Subnet mask [IP Address]
Set a subnet mask. If it has already been set, currently set subnet mask is displayed.
EtherNet/IP Gateway IP address [IP Address]
Set a subnet mask. If it has already been set, currently set subnet mask is displayed.
EtherNet/IP Bit Rate
Set the EtherNet/IP communication speed.
EtherNet/IP Bit Rate |
Set
automatically according to the connected device |
100Mbps Full Duplex |
100Mbps Half Duplex |
10Mbps Full Duplex |
10Mbps Half Duplex |
---|---|---|---|---|---|
Value | 0 (Default Setting) | 1 | 2 | 3 | 4 |
EtherNet/IP Insensitive time to network error [ms]
If the Communication check of EtherNet/IP communication starts too early after the Robot controller startup, an error [8350200B Prepare for field network communication] might be displayed immediately after booting.
To prevent such error, adjust "EtherNet/IP Insensitive time to network error" of Fieldbus parameter longer.
EtherNet/IP Insensitive time to network error [ms] | Available range | Default Setting |
---|---|---|
Value | 0~65535 | 22000 |
EtherNet/IP DHCP Enable
If this parameter is enabled, an IP address used by EtherNet/IP is automatically obtained by DHCP.
EtherNet/IP DHCP Enable | Enable | Disable (Default Setting) |
---|---|---|
Value | 1 | 0 |
EtherNet/IP ErrDisplay
This parameter allows you to choose whether the network error will display in "every time" or is display at the "first time" only.
This parameter is set to "0" (EveryTime) by default for safe operation of the facilities. Every time an I/O operation is carried out, an error will display if any.
To check program operations using dummy I/Os for setting up facilities where no connection to the network has been established, set this parameter to "1" (First Time). Doing so will not display errors once detected, allowing you to check program operations.
EtherNet/IP ErrDisplay | First Time | EveryTime (Default Setting) |
---|---|---|
Value | 1 | 0 |
EtherNet/IP Input Run/Idle Header
Set this parameter when the top of the Input data from the EtherNet/IP Master shifts 32bits from the I/O port No. 512.
EtherNet/IP Input Run/Idle Header |
Enable | Disable (Default Setting) |
---|---|---|
Value | 1 | 0 |
EtherNet/IP Output Run/Idle Header
Set this parameter when the Output data of EtherNet/IP Master shifts by 32bit on the master side.
EtherNet/IP Output Run/Idle Header |
Enable | Disable (Default Setting) |
---|---|---|
Value | 1 | 0 |
ID : 5835
- Related Information
- Connection with the Rockwell Automation PLC