Contactor Contact Monitor (output)

Function

This signal outputs the status of the auxiliary contact of the motor contactor in the robot controller. For signals Contactor Contact Monitor 1a and Contactor Contact Monitor 2a, the contact output signal comes ON when the motor is turned on; it comes OFF when the motor is turned off. For signals Contactor Contact Monitor 1b and Contactor Contact Monitor 2b, the contact output signal comes OFF when the motor is turned on; it comes ON when the motor is turned off.

Terminal number

Signal name Terminal number
Contactor Contact Monitor 1b #6 and #40 on Mini I/O connector
Contactor Contact Monitor 2b #7 and #41 on Mini I/O connector
Contactor Contact Monitor 1a #10 and #44 on Mini I/O connector
Contactor Contact Monitor 2a #27 and #61 on Mini I/O connector

Usage

This signal is used to confirm the ON/OFF state of the motor on the monitor.
For details about the emergency stop circuits, refer to the I/O MANUAL (for Mini I/O), following clause "External Emergency Stop and Enable Auto Input Circuits"and "Emergency Stop Circuit", according to the I/O type NPN or PNP.

  • It takes 40 milliseconds from the turning-ON of the Contactor Contact Monitor 1 to the turning-ON of the Contactor Contact Monitor 2.
  • Apply at least 10 milliamperes through the contacts.