ID : 10875
Specifications and I/O Allocation
Specifications
| Item | Specifications | |||
|---|---|---|---|---|
| Communications protocol | DeviceNet-compliant | |||
| Connection supported | Master/slave connection : Polling I/O function Compliant with DeviceNet communications rules | |||
| Connection type *1 | Multi-drop type with possible combination of T-branch (to trunk and branch lines) | |||
| Bit rate | 500, 250, 125 kbps | |||
| Communications media | Special cable consisting of 5 wires (2 for signals, 2 for power supply and 1 as a shield wire) | |||
|
Communications cable length |
Bit rate | Max. network length | Branch length | Total branch length |
| 500 kbps | 100 m or less *2 | 6 m or less | 39 m or less | |
| 250 kbps | 250 m or less *2 | 6 m or less | 78 m or less | |
| 125 kbps | 500 m or less *2 | 6 m or less | 156 m or less | |
| Power supply for communication | External supply of 24 VDC ±10 % | |||
| Internal power consumption | Communication power source: 65 mA max. | |||
| Max. number of connectable nodes | 64 nodes (including configurator (converter) if connected) | |||
| Number of system inputs | 40 points | |||
| Number of system outputs | 32 points | |||
| Number of user inputs (The number of I/Os can be set in unit of 8 points.) |
0 to 216 points | |||
| Number of user outputs (The number of I/Os can be set in unit of 8 points.) |
0 to 224 points | |||
| Error check | CRC | |||
*1 Terminator resistors are needed at both ends of the trunk line. (121 Ω) *2 These values may apply when a special thick cable is used as a trunk line. If a special fine cable is used, the maximum network length is 100 m or less. |
||||
I/O Allocation
The port numbers of DeviceNet slave terminal are 512 to 767 for input ports and 768 to 1023 for outputs port.
| Standard | |
|---|---|
ID : 10875
- Related Information
- Input Data
- Output Data