ID : 7933
Field Bus Parameter Setting
With a Remote TP/Virtual TP, set the field network communication.
Operation path : Top window - [F4 I/O] - [F6 Aux] - [F4 Field Bus parameter]
440: PROFINET ErrDisplay
This parameter allows you to choose whether the network error will display in "every time" or is display at the "first time" only.
This parameter is set to "0" (EveryTime) by default for safe operation of the facilities. Every time an I/O operation is carried out, an error will display if any.
To check program operations using dummy I/Os for setting up facilities where no connection to the network has been established, set this parameter to "1" (FirstTime). Doing so will not display errors once detected, allowing you to check program operations.
Value | |
---|---|
0 | EveryTime (Default Setting) |
1 | FirstTime |
441: PROFINET Insensitive time to network error [ms]
If the communication check of PROFINET communication starts too early after the COBOTTA startup, an error [8350200B: Prepare for field network communication] might be displayed immediately after booting.
To prevent such error, adjust "PROFINET Insensitive time to network error" of Fieldbus parameter longer.
Available range | 0 to 65535 |
---|---|
Default Setting | 20000 |
ID : 7933