ID : 5840
Field Bus Parameter Setting
Set the robot controller with teach pendant.
From the top screen—[F4 I/O]—[F6 Aux.]-[F4 Field Bus parameter]
EtherCAT Insensitive time to network error
If the Communication check of EtherCAT communication starts too early after the Robot controller startup, an error [8350200B Prepare for field network communication] might be displayed immediately after booting.
To prevent such error, adjust "EtherCAT Insensitive time to network error" of Fieldbus parameter longer.
EtherCAT Insensitive time to network error [ms] | Available range | Default Setting |
---|---|---|
Value | 0~65535 | 20000 |
EtherCAT ErrDisplay
This parameter allows you to choose whether the network error will display in "every time" or is display at the "first time" only.
This parameter is set to "0" (EveryTime) by default for safe operation of the facilities. Every time an I/O operation is carried out, an error will display if any.
To check program operations using dummy I/Os for setting up facilities where no connection to the network has been established, set this parameter to "1" (First Time). Doing so will not display errors once detected, allowing you to check program operations.
EtherCAT ErrDisplay | First Time | EveryTime (Default Setting) |
---|---|---|
Value | 1 | 0 |
EtherCAT Station Address
Set the node address of EtherCAT.
EtherCAT Station Address |
Manual setting | Auto-setting by Master Default Setting) |
---|---|---|
Value | 1~65535 | 0 |
ID : 5840