Field Bus Parameter Setting

With a Remote TP/Virtual TP, set the field network communication.

Operation path : Top window - [F4 I/O] - [F6 Aux] - [F4 Field Bus parameter]

451: EtherCAT Insensitive time to network error

If the communication check of EtherCAT communication starts too early after the COBOTTA startup, an error [8350200B: Prepare for field network communication] might be displayed immediately after booting.
To prevent such error, adjust "EtherCAT Insensitive time to network error [ms]" of Fieldbus parameter longer.

Available range 0 to 65535
Default Setting 20000

452: EtherCAT ErrDisplay

This parameter allows you to choose whether the network error will display in "every time" or is display at the "first time" only.

This parameter is set to "0" (EveryTime) by default for safe operation of the facilities. Every time an I/O operation is carried out, an error will display if any.
To check program operations using dummy I/Os for setting up facilities where no connection to the network has been established, set this parameter to "1" (FirstTime). Doing so will not display errors once detected, allowing you to check program operations.

Value
0 EveryTime (Default Setting)
1 FirstTime
After completion of setting-up, be sure to set this parameter back to "0."

453: EtherCAT Station Address

Set the node address of EtherCAT.

Value Description
1 to 65535 Manual setting
0 Auto-setting by Master (Default Setting)