<< Prev        

ID : 5890

I/O Port Map and Allocation

Using the I/O conversion box allocates the area of the 1st parallel I/O board mounted to I/O port #0 to #127, so the standard area allocation is changed as listed below.

I/O port number Allocation Area
0 ~ 45 Parallel input Standard area
46 ~ 47 Not used.
48 ~ 55 Input by hand
56 ~ 63 Not used.
64 ~ 71 Output by hand
72 ~ 127 Parallel output
128 ~ 511 Internal I/O
512 ~ 767

CC-Link remote device input

DeviceNet slave input

EtherNet/IP Adapter input

PROFIBUS slave input

PROFINET IO Device input

EtherCAT slave input

I/O extension board area
768 ~ 1023

CC-Link remote device output

DeviceNet slave output

EtherNet/IP Adapter output

PROFIBUS slave output

PROFINET IO Device output

EtherCAT slave output

1024 ~ 2047 DeviceNet master input
2048 ~ 3071 DeviceNet master output
3072 ~ 3327 Not used.
3328 ~ 3583 Not used.
3584 ~ 3623 Parallel I/O board input
3624 ~ 3839 Not used.
3840 ~ 3887 Parallel I/O board output
3888 ~ 4095 Not used.
4096 ~ 7871

CC-Link remote device

  • CC-Link Ver.1.10

4096 ~ 4351 : CC-Link remote device input

4352 ~ 4607 : Not used.

4608 ~ 4863 : CC-Link remote device output

4864 ~ 7871 : Not used.

  • CC-Link Ver.2.00

4096 ~ 6783 : CC-Link remote device input

6784 ~ 7871 : Not used.

EtherNet/IP Adapter input

PROFINET IO Device input

EtherCAT slave

4096 ~ 5887 : EtherCAT slave input

5888 ~ 7871 : Not used.

7872 ~ 11647

CC-Link remote device

  • CC-Link Ver.2.00

7872 ~ 10559 : CC-Link remote device output

10560 ~ 11647 : Not used.

EtherNet/IP Adapter output

PROFINET IO Device output

EtherCAT slave

7872 ~ 9663 : EtherCAT slave output

9664 ~ 11647 : Not used.

11648 ~ 15807 PROFINET IO Device input
15808 ~ 19903 Not used.
19904 ~ 24063 PROFINET IO Device output

ID : 5890

<< Prev