ID : 5118
Field Bus Parameter Setting
Set the robot controller with teach pendant.
From the top screen—[F4 I/O]—[F6 Aux.]-[F4 Field Bus parameter]
PROFIBUS node address (1-125)
Set the PROFIBUS node address.
PROFIBUS node address (1-125) | Available range | Default Setting |
---|---|---|
Value |
1 to 125 | 1 |
PROFIBUS ErrDisplay
This parameter allows you to choose whether the network error will display in "every time" or is display at the "first time" only.
This parameter is set to "0" (EveryTime) by default for safe operation of the facilities. Every time an I/O operation is carried out, an error will display if any.
To check program operations using dummy I/Os for setting up facilities where no connection to the network has been established, set this parameter to "1" (First Time). Doing so will not display errors once detected, allowing you to check program operations.
PROFIBUS ErrDisplay | First Time | EveryTime (Default Setting) |
---|---|---|
Value | 1 | 0 |
PROFIBUS Insensitive time to network error [ms]
If the Communication check of PROFIBUS communication starts too early after the Robot controller startup, an error [8350200B Prepare for field network communication] might be displayed immediately after booting.
To prevent such error, adjust "PROFIBUS Insensitive time to network error" of Fieldbus parameter longer.
PROFIBUS Insensitive time to network error [ms] | Available range | Default Setting |
---|---|---|
Value | 0 to 65535 | 20000 |
ID : 5118
- Related Information
- Obtaining a GSD File