<< Prev        Next >>

ID : 1456

Specifications

The following tables list the controller environmental and communication specifications.

Environmental Requirements

Item Specifications
Operating temperature 0 to 40 ℃
Operating humidity 90 % RH or less (without condensation)

DeviceNet Communications Specifications

Item Specifications
Communications protocol DeviceNet-compliant
Connection supported Master/slave connection : Polling I/O function Compliant with DeviceNet communications rules
Connection type *1 Multi-drop type with possible combination of T-branch (to trunk and branch lines)
Bit rate 500, 250, 125 kbps
Communications media Special cable consisting of 5 wires (2 for signals, 2 for power supply and 1 as a shield wire)

Communications cable length

Bit rate Max. network length Branch length Total branch length
500 kbps 100 m or less *2 6 m or less 39 m or less
250 kbps 250 m or less *2 6 m or less 78 m or less
125 kbps 500 m or less *2 6 m or less 156 m or less
Power supply for communication External supply of 24 VDC ±10 %
Internal power consumption Communication power source: 65 mA max.­
Max. number of connectable nodes 64 nodes (including configurator (converter) if connected)
  Standard allocation Compatible allocation
Number of system inputs 40 points 24 points
Number of system outputs 32 points 32 points
Number of user inputs
(The number of I/Os can be set in unit of 8 points.)
0 to 216 points 16 to 232 points
Number of user outputs
(The number of I/Os can be set in unit of 8 points.)
0 to 224 points 0 to 224 points
Error check CRC

*1 Terminator resistors are needed at both ends of the trunk line. (121 Ω)

*2 These values may apply when a special thick cable is used as a trunk line. If a special fine cable is used, the maximum network length is 100 m or less.

ID : 1456

<< Prev        Next >>