The following table shows parameters used for the RC8A Safety motion specification. This parameter is available Ver. 2.1.* or higher.

Setting with the WINCAPSIII

To set parameters, use WINCAPSIII. It is impossible to set parameters with a teach pendant.

For details about operation, refer to Setting for Monitoring of RC8A Safety Motion Specification Manual.

Parameter List

No. Item Name Unit Default Description
2 Enable Auto input - 1

Specify whether to use the Enable auto input or not.

0 : Disable
1 : Enable (use this signal)

3 SS2 input setting - 1

Specify whether to use the SS2 input signal or not.

0 : Disable
1 : Enable (use this signal)

4 RSM1 input setting - 1

Specify whether to use the RSM1 input signal or not.

0 : Disable
1 : Enable (use this signal)

5 RSM2 input setting - 1

Specify whether to use the RSM2 input signal or not.

0 : Disable
1 : Enable (use this signal)

6 RSM3 input setting - 1

Specify whether to use the RSM3 input signal or not.

0 : Disable
1 : Enable (use this signal)

7 TOOL0 input setting - 1 Specify whether to use the TOOL0 input signal or not.

0 : Disable
1 : Enable (use this signal)

8 TOOL1 input setting - 1 Specify whether to use the TOOL1 input signal or not.

0 : Disable
1 : Enable (use this signal)

9 TOOL2 input setting - 1 Specify whether to use the TOOL2 input signal or not.

0 : Disable
1 : Enable (use this signal)

10 TOOL3 input setting - 1 Specify whether to use the TOOL3 input signal or not.

0 : Disable
1 : Enable (use this signal)

11 Monitoring area 0 disable input setting - 1

Specify whether to use the Monitoring area 0 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

12 Monitoring area 1 disable input setting - 1

Specify whether to use the Monitoring area 1 dusable input signal or not.

0 : Disable
1 : Enable (use this signal)

13 Monitoring area 2 disable input setting - 1

Specify whether to use the Monitoring area 2 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

14 Monitoring area 3 disable input setting - 1

Specify whether to use the Monitoring area 3 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

15 Monitoring disable input setting - 0

Specify whether to use the Monitoring disable input signal or not.

0 : Disable
1 : Enable (use this signal)

16 SS1 input setting - 1 Specify whether to use the SS1 input signal or not.

0 : Disable
1 : Enable (use this signal)

17 Safe reference position check input setting - 1 Specify whether to use the Safe reference position check input signal or not.

0 : Disable
1 : Enable (use this signal)

18 SLP output setting - 1 Specify whether to use the SLP output signal or not.

0 : Disable
1 : Enable (use this signal)

19 RSM1 output setting - 1 Specify whether to use the RSM1 output signal or not.

0 : Disable
1 : Enable (use this signal)

20 RSM2 output setting - 1 Specify whether to use the RSM1 output signal or not.

0 : Disable
1 : Enable (use this signal)

21 RSM3 output setting - 1 Specify whether to use the RSM1 output signal or not.

0 : Disable
1 : Enable (use this signal)

22 RPM output setting - 1 Specify whether to use the RPM output signal or not.

0 : Disable
1 : Enable (use this signal)

23 SOS output setting - 1 Specify whether to use the SOS output signal or not.

0 : Disable
1 : Enable (use this signal)

24 Safe reference position check output setting - 1 Specify whether to use the Safe reference position check output signal or not.

0 : Disable
1 : Enable (use this signal)

25 Auto mode output setting - 1 Specify whether to use the Auto mode outout signal or not.

0 : Disable
1 : Enable (use this signal)

28 Area sensor SS2 input setting - 0

Specify whether to use the Area sensor SS2 input signal or not.

0 : Disable
1 : Enable (use this signal)

29 Area sensor RSM1 input setting - 0 Specify whether to use the Area sensor RSM1 input signal or not.

0 : Disable
1 : Enable (use this signal)

30 Area sensor RSM2 input setting - 0 Specify whether to use the Area sensor RSM2 input signal or not.

0 : Disable
1 : Enable (use this signal)

31 Area sensor RSM3 input setting - 0 Specify whether to use the Area sensor RSM3 input signal or not.

0 : Disable
1 : Enable (use this signal)

32 Area sensor TOOL0 input setting - 0 Specify whether to use the Area sensor TOOL0 input signal or not.

0 : Disable
1 : Enable (use this signal)

33 Area sensor TOOL1 input setting - 0 Specify whether to use the Area sensor TOOL1 input signal or not.

0 : Disable
1 : Enable (use this signal)

34 Area sensor TOOL2 input setting - 0 Specify whether to use the Area sensor TOOL2 input signal or not.

0 : Disable
1 : Enable (use this signal)

35 Area sensor TOOL3 input setting - 0 Specify whether to use the Area sensor TOOL3 input signal or not.

0 : Disable
1 : Enable (use this signal)

36 Area sensor monitoring area 0 disable input setting - 0 Specify whether to use the Area sensor monitoring area 0 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

37 Area sensor monitoring area 1 disable input setting - 0 Specify whether to use the Area sensor monitoring area 1 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

38 Area sensor monitoring area 2 disable input setting - 0 Specify whether to use the Area sensor monitoring area 2 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

39 Area sensor monitoring area 3 disable input setting - 0 Specify whether to use the Area sensor monitoring area 3 disable input signal or not.

0 : Disable
1 : Enable (use this signal)

40 Area sensor monitoring disable input setting - 0 Specify whether to use the Area sensor monitoring disable input signal or not.

0 : Disable
1 : Enable (use this signal)

41 Area sensor SS1 input setting - 0 Specify whether to use the Area sensor SS1 input signal or not.

0 : Disable
1 : Enable (use this signal)

42 Area sensor Safe Homing input setting - 0 Specify whether to use the Area sensor Safe Homing input signal or not.

0 : Disable
1 : Enable (use this signal)

66 SLP Setting - 255

Specify to enable/disable the SLP function for each axis by bit-unit. For each bit value, "1" is enable, "0" is disable.

As a default, all axes are enabled.

0 bit : 1st axis
1 bit : 2nd axis
2 bit : 3rd axis
3 bit : 4th axis
4 bit : 5th axis
5 bit : 6th axis
6 bit : 7th axis
7 bit : 8th axis

(Example 1) If you enable 1st to 6th axis and disable 7th and 8th axis, 0 to 5 bits are "1" and 6 and 7 bits are "0", therefore specify "63".

(Example 2) If you disable 7th axis only, only 6 bit is "0", therefore specify "191".

70 Max payload setting(*1) g 0 Enter the total mass of tool and work.
Enter the expected maximum Mass of Payload value where User parameter (No.1) or Payload command would specify for the actual application.
71 Servo response delay at Emergency stop ms 32

Parameter to adjust the expected position of the SLP function and RPM function.

If you set larger value for this parameter, the detection timing of the above safety function will be earlier. For example, if a robot enters a certain monitoring area, when larger value is set for this parameter, the SS1 function will work at the timing earlier than before setting larger value.

This parameter does not adjust the emergency-stop input (including emergency-stop button) processing. Therefore, even if you change this parameter, it will not affect the stopping time and distance at an emergency stop by the emergency-stop input (including the emergency-stop button).

If you change this parameter, please make sure to check the motion in order to secure operator’s safety.

89 Safe reference position (J1) deg. mm 0.000 Enter the Safe reference position (J1).
90 Safe reference position (J2) deg. mm 0.000 Enter the Safe reference position (J2).
91 Safe reference position (J3) deg. mm 0.000 Enter the Safe reference position (J3)
92 Safe reference position (J4) deg. mm 0.000 Enter the Safe reference position (J4)
93 Safe reference position (J5) deg. mm 0.000 Enter the Safe reference position (J5)
94 Safe reference position (J6) deg. mm 0.000 Enter the Safe reference position (J6)
95 Safe reference position (J7) deg. mm 0.000 Enter the Safe reference position (J7)
96 Safe reference position (J8) deg. mm 0.000 Enter the Safe reference position (J8)
97 Safe reference position tolerance (J1) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J1)
98 Safe reference position tolerance (J2) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J2)
99 Safe reference position tolerance (J3) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J3)
100 Safe reference position tolerance (J4) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J4)
101 Safe reference position tolerance (J5) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J5)
102 Safe reference position tolerance (J6) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J6)
103 Safe reference position tolerance (J7) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J7)
104 Safe reference position tolerance (J8) deg. mm 0.010 Enter the maximum allowable deviation in degree or millimeter from the Safe reference position under the Safe reference position check function. (J8)
105 Positional tolerance while Power-OFF (J1) deg. mm 0.010

Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J1)

106 Positional tolerance while Power-OFF (J2) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J2)
107 Positional tolerance while Power-OFF (J3) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J3)
108 Positional tolerance while Power-OFF (J4) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J4)
109 Positional tolerance while Power-OFF (J5) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J5)
110 Positional tolerance while Power-OFF (J6) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J6)
111 Positional tolerance while Power-OFF (J7) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J7)
112 Positional tolerance while Power-OFF (J8) deg. mm 0.010 Enter the maximum allowable positional difference between controller power-OFF and power-ON under the Safe reference position check function. (J8)

*1: In the Safety motion specification, if [Mass of payload] of Setting condition (User parameter) is smaller than [Max payload setting] of Safety-related parameters, an error occurs at the controller startup. Also, if [Max payload setting] of Safety-related parameters is smaller than the [Mass of payload] of the designated item, an error occurs at the execution of Payload command. (Available for Ver.2.5.* or later)