Solenoid Valve Specifications

Valves

Switching system

2-position, Double Solenoids

3-position, Exhaust Center Solenoids

3-position, Closed Center Solenoids

Applicable fluid Air
Operating system Pilot type
Effective cross section (Cv value)

P->A・B:1.116 mm² (0.062)
A・B->R:1.188 mm² (0.066)

Lubrication Oilless
Operating pressure range 0.2 to 0.7 MPa *
Response time 15 ms or below(when operating pressure is 0.5 MPa)
Maximum operating frequency 10 Hz
Ambient temperature -5 to 50°C (No dew condensation allowed. When dry air is used.)

* The air source to be connected to the robot unit should be used within the operating pressure range from 0.20 to 0.39 MPa.

Solenoids

Operating voltage 24 V +/- 10%
Power consumption (current) 0.5 W (21 mA)
Surge voltage protection circuit Zener diode

Switching System: 2-Position, Double Solenoid

When both solenoids A and B are deenergized, the valve holds its position.

This system is available for the VS-050 / 060 / 068 / 087.

A, B Air outlet to tools
P Air inlet from AIR1
EA, EB

To exhaust ports

For clean room type, these are connected to “VALVE-OUT” (AIR2) of a connector panel.

Switching System: 3-Position, Exhaust Center Solenoid

When both solenoids A and B are deenergized or when the power is OFF, the valve is in the center position to exhaust the residual pressure of solenoids A and B.

This system is available for the VS-068 / 087.

Switching System: 3-Position, Closed Center Solenoid

When both solenoids A and B are deenergized or when the power is OFF, the valve is in the center position to hold the residual pressure of solenoids A and B.

This system is available for the VS-068 / 087.

In preparation for maintenances or an emergency, install an equipment to release the residual pressure between the hand and the valve by customer side.

The Valve Exhaust Port

Do not cover the valve exhaust port on the second arm.