ID : 1499
Original Position
When you change the original position, a machine reference over error may occur. In this case, execute machine reference clear.
Direction for returning the fingers to their original positions
This parameter is used for specifying the direction in which the fingers return to their original positions.
0: Opening direction 1: Closing direction
If setting the direction in which the fingers return to their original positions to “0: OPEN”, the closing direction will become a positive direction, then the fingers move in the closing direction.
If the direction in which the fingers return to their original positions is set to the opening direction, the closing direction will become positive direction.
Speed for returning the fingers to their original positions
This parameter is used for setting the speed at which the fingers move back to their original positions.
Input rage: 20~50(%)
Initial value: 20%
Original position shift
This parameter is used for shifting the coordinate position of original data by the parameter value specified as original position shift.
Input range: -99.99~99.99 (in 0.01mm)
Initial value: 0
If this parameter is specified, there is no need to reentry point data in the case of misalignment of original positions during product maintenance. Zero point shift should be set within the soft limit.
Original position return system
This parameter is used for changing the method in which the fingers return to their original positions.
0: Stroke end
1: S stroke end + Z phase detection system
Initial value: 1
ID : 1499